For UMCS, IDS, ESS and similar systems requiring
head-end computers and software, designer shall use
the paragraph DELIVERY OF TECHNICAL DATA and delete
paragraph SUBMITTALS. In no case will both
paragraphs be retained.
**************************************************************************
Computer software and technical data (including technical data which
relates to computer software), which are specifically identified in this
specification shall be delivered strictly in accordance with the CONTRACT
CLAUSES, SPECIAL CONTRACT REQUIREMENTS, and in accordance with the Contract
Data Requirements List (CDRL), DD Form 1423, which is attached to and
thereby made a part of this contract. All data delivered shall be
identified by reference to the particular specification paragraph against
which it is furnished. If the DTS is being installed in conjunction with
system, closed circuit television system, or utility monitoring and control
system, the Technical Data Packages shall be submitted as part of the
Technical Data Package for Section [_____]; [_____] hard copies and [_____]
electronic copies (DC-ROM or DVD-R) of the Technical Data Package(s) shall
be submitted.
1.4.1
Group I Technical Data Package
1.4.1.1
System Drawings
The package shall include the following:
b. FO receivers, transmitters, transceivers, multiplexers, and FO modem
c. FO receivers, transmitters, transceivers, multiplexers, and FO modem
physical layout and schematics.
f. Details of surge protection device installations.
g. Details of cable splicing and connector installations.
h. Details of aerial cable and messenger installation on poles, cable
entrance to buildings, and termination inside enclosures.
i. Details of underground cable and duct installation, cable entrance
into buildings, and terminations inside enclosures.
Drawings shall show proposed layout and anchorage of equipment and
appurtenances, and equipment relationship to other parts of the work
including clearance for maintenance and operations. System drawings shall
show proposed configuration, including location, type and termination of
both interior and exterior fiber optics and showing the location, duct and
innerduct arrangement, and fiber assignment. The ac power consumption and
heat dissipation shall be shown under both normal and maximum operating
conditions.
SECTION 16768A
Page 12