shall be installed according to Chapter 5 of NFPA 70 and as shown.
1.3.4
Electrical Requirements
The equipment shall operate from a voltage source as shown, plus or minus
10 percent, and 60 Hz, plus or minus 2 percent.
1.3.5
Input Line Surge Protection
Inputs and outputs shall be protected against surges induced on wiring and
cables including wiring and cables installed outdoors. Surge protection
devices shall be selected based on voltages and current ratings of
against surges induced on any communications circuit. Cables and
conductors (except non-conductive fiber optic cables which serve as
equipment), shall have surge protection circuits installed at each end.
Protection shall be furnished at equipment, and additional triple electrode
gas surge protectors rated for the application on each conductive wire line
and coaxial circuit shall be installed within 1 meter 3 feet of the
on voltages and current ratings of components to be protected. Fuses shall
not be used for surge protection. The inputs and outputs shall be tested
in both normal mode and common mode using the following two waveforms:
a. A 10 microsecond rise time by 1000 microsecond pulse width waveform
with a peak voltage of 1500 volts and a peak current of 60 amperes.
b. An 8 microsecond rise time by 20 microsecond pulse width waveform
with a peak voltage of 1000 volts and a peak current of 500 amperes.
1.3.6
Power Line Surge Protection
Equipment connected to AC circuits shall be protected from power line
current ratings of components to be protected. Equipment shall meet the
requirements of IEEE C62.41. Fuses shall not be used for surge protection.
1.3.7
Spare Parts
The Contractor shall submit spare parts data for each different item of
material and equipment specified and furnished, after approval of detail
drawings not later than [_____] months prior to the date of beneficial
occupancy. The data shall include a list of parts and supplies, with
current unit prices and source of supply, and a list of the parts
recommended by the manufacturer to be replaced after [1 year] [3 years] of
service.
1.4
DELIVERY OF TECHNICAL DATA
**************************************************************************
NOTE: Insert the Section title of the appropriate
additional specifications: Section 16751A CLOSED
CIRCUIT TELEVISION SYSTEMS; Section 13702N BASIC
INTRUSION DETECTION SYSTEMS (IDS); Section 13703N
COMMERCIAL INTRUSION DETECTION SYSTEMS (IDS);
Section 13720A ELECTRONIC SECURITY SYSTEM; Section
13721A SMALL INTRUSION DETECTION SYSTEM; Section
13801A UTILITY MONITORING AND CONTROL SYSTEMS (UMCS).
SECTION 16768A
Page 11