designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control
approval.] [information only. When used, a designation following the "G"
designation identifies the office that will review the submittal for the
Government.] The following shall be submitted in accordance with Section
01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fiber Optic System[; G][; G, [_____]]
Installation[; G][; G, [_____]]
material, including manufacturer's descriptive and technical
literature, performance charts and curves, catalog cuts, and
required to demonstrate that the system has been coordinated and
will properly function with its associated subsystems as well as
other systems. Drawings shall show proposed layout and anchorage
of equipment and appurtenances, and equipment relationship to
other parts of the work including clearance for maintenance and
operations. System drawings shall show proposed configuration,
including location, type and termination of both interior and
exterior fiber optics and showing the location, duct and innerduct
arrangement, and fiber assignment. The ac power consumption and
heat dissipation shall be shown under both normal and maximum
operating conditions.
SD-03 Product Data
Fiber Optic System
Equipment calculations for flux budgets and gain margins.
Spare Parts
Data lists of spare parts, tools, and test equipment, as
specified.
Manufacturer's Instructions[; G][; G, [_____]]
Where installation procedures, or any part thereof, are required
SECTION 16768A
Page 8