engine-generator set power.
a.
Approximate exhaust temperature degrees C F at full load
b.
Weight of exhaust gas at full load kg per hr lb per hr
c.
Weight of intake air at full load kg per hr lb per hr
d.
Total heat rejected at full load kW Btu per hr
1.
To jacket coolant system
2.
e.
Emissions (Lbs/hr)(kg/hr) at full load
1.
Total Suspended Particulate
2.
Particulate matter with an average aerodynamic diameter of 10
microns (PM-10)
3.
Sulfur dioxides
4.
5.
Carbon Monoxide
6.
Volatile Organic Compounds
f.
Visible Emissions (percent opacity) at full load
1.3.4
Submit data certified by the generator manufacturer including but not
limited to the following:
a.
b.
kW rating of generator
c.
Generator reactances
1.
Synchronous reactance, Xd
2.
Transient reactance,
X'd
3.
Subtransient reactance, X"d
4.
Negative sequence reactance, X2
5.
Zero sequence reactance, Xo
1.3.5
Capacity Calculations for Engine-Generator Set
Calculations shall verify that the engine-generator set power rating is
adequate for the load described in the paragraph entitled "Load Profile."