oil cooler, or jacket coolant water systems (i.e.,
the engine-generator set is installed internal to a
building in lieu of in a self contained outdoor
enclosure), include the following paragraph.
**************************************************************************
Submit drawings showing floor plan arrangement of[ exhaust,][ air intake,][
fuel oil cooler,][ and][ jacket coolant water] systems including
arrangement of piping and pipe sizes.
]1.5.2
Vibration Isolation System Certification
Submit certification from the manufacturer that the vibration isolation
system will reduce the vibration to the limits specified in the paragraph
entitled "Vibration Isolation System."
1.5.3
Fuel System Certification
When the diesel fuel system requires a fuel oil cooler as described in the
paragraph entitled "Fuel Oil Cooler," submit certification from the engine
manufacturer that the fuel system design is satisfactory.
1.6
DELIVERY, STORAGE, AND HANDLING
Deliver equipment on pallets or blocking wrapped in heavy-duty plastic,
sealed to protect parts and assemblies from moisture and dirt. Plug
piping, conduit, exhaust, and air intake openings. Protect and prepare
batteries for shipment as recommended by the battery manufacturer. Store
1.7
SITE CONDITIONS
Protect the components of the engine-generator set, including cooling
system components, pumps, fans, and similar auxiliaries when not operating
and provide components capable of the specified outputs in the following
environment:
a.
Site Location:
[_____]
b.
Site Elevation:
[_____] meters[_____] feet above mean sea level
c.
Ambient Temperatures:
**************************************************************************
NOTE: Ambient temperatures, design wind velocity,
and prevailing wind direction shall be as defined by
NAVFAC P-89, "Engineering Weather Data," dated 1
July 1978.
**************************************************************************
1.
Maximum [_____] degrees C[_____] degrees F dry bulb, [_____]
degrees C[_____] degrees F wet bulb.
2.
Minimum [_____] degrees C[_____] degrees F dry bulb.
[d.
Design Wind Velocity:
[_____] km/h[_____] mph.]
[e.
Prevailing Wind Direction:
[_____].]
SECTION 16237N