2. Piping for ventilation of engine crankcase to
atmosphere where required.
3. Details of exhaust, cooling water, and fuel
piping, including penetrations through walls and
roofs showing piping sleeves and exterior flashing
where applicable.
4.
Diesel fuel day tank capacity where applicable.
5. Location of remote alarm annunciator where
applicable.
6. Circuiting for the jacket coolant heating
system, electric motor driven radiator fan where
applicable, diesel fuel day tank system, starting
battery charger, remote alarm annunciator storage
battery charger where applicable, and generator
space heater.
7. Grounding plan. For applications using transfer
switches, the transfer switch shall be four pole and
the generator shall be grounded as a separately
derived system.
**************************************************************************
PART 1
GENERAL
1.1
REFERENCES
**************************************************************************
NOTE: Issue (date) of references included in
provided by the latest guide specification. Use of
SpecsIntact automated reference checking is
recommended for projects based on older guide
specifications.
**************************************************************************
The publications listed below form a part of this specification to the
extent referenced. The publications are referred to within the text by the
basic designation only.
ASME INTERNATIONAL (ASME)
ASME B16.1
Fittings
ASME B16.21
(1992) Nonmetallic Flat Gaskets for Pipe
Flanges
ASME B16.3
(1998) Malleable Iron Threaded Fittings
ASME B16.5
(2003) Pipe Flanges and Flanged Fittings
ASME B16.9
(2003) Factory-Made Wrought Steel
Buttwelding Fittings
SECTION 16237N
Page 5