i.
Piston speed, m/s fpm.
j.
kW power rating of engine-generator set as defined in the paragraph
entitled "Engine-Generator Set Ratings and Performance."
k.
Induction method (naturally aspirated, turbocharged).
l.
Intercooler type (air-to-air or jacket water).
m.
Governor type, make, and model.
n.
Make and model of turbochargers.
1.3.2
Engine-Generator Set Efficiencies
**************************************************************************
NOTE: Include the bracketed option below for
projects located outside the continental United
States (OCONUS)
**************************************************************************
Submit data pertaining to the diesel engine-generator set including but not
limited to the following: Loads shall be calculated on basis of rated
engine-generator set power.
a.
Fuel consumption at 0.80 power factor, liters per hr gallons per hr.
1.
1/2 load
2.
3/4 load
3.
Full load
b.
Generator efficiency at 0.80 power factor (percent)[ in accordance with
IEC 60034-2].
1.
1/2 load
2.
3/4 load
3.
Full load
c.
Radiator capacity at design conditions.
1.
Coolant shall be antifreeze mixture as specified under paragraph
2.
L/s gpm of coolant
3.
L/s cfm of air through radiator
4.
kW Btu per hr of heat exchange based on optimum coolant
temperature to and from engine.
1.3.3
Diesel Engine Data
Submit data certified by the engine manufacturer including but not limited
to the following: Loads shall be calculated on basis of rated
SECTION 16237N
Page 9