Camps and Stations
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
40 CFR 60
Standards of Performance for New
Stationary Sources
UNDERWRITERS LABORATORIES (UL)
UL 1236
(2002) Battery Chargers for Charging
Engine-Starter Batteries
UL 142
(2002) Steel Aboveground Tanks for
UL 429
(1999; Rev thru Feb 2004) Electrically
Operated Valves
UL 467
(2004) Grounding and Bonding Equipment
UL 489
(2002; Rev thru May 2003) Molded-Case
and Circuit-Breaker Enclosures
1.2
RELATED REQUIREMENTS
Section 16050N BASIC ELECTRICAL MATERIALS AND METHODS, and Section 16081
APPARATUS INSPECTION AND TESTING apply to this section except as modified
herein.
1.3
SYSTEM DESCRIPTION
1.3.1
Submit data pertaining to the diesel engine-generator set and to the
a.
Make of engine.
b.
Type or model of engine.
c.
Gross bhp rating of engine shall be the total rated power output before
engine driven radiator fan.
d.
Net brake power rating of engine shall include deductions for the total
power requirements of electric motor-driven or engine-driven
accessories as defined in ISO 3046. Net ratings shall include a
including radiator fans and any other power consuming devices required
to provide cooling as specified.
e.
Strokes per cycle.
f.
Number of cylinders.
g.
Bore and stroke, mm inches.
h.
Engine speed, rpm.
SECTION 16237N