during the warranty period of the contract.
1.8
POSTED OPERATING INSTRUCTIONS
Provide for each system and principal item of equipment as specified in the
technical sections for use by operation and maintenance personnel. The
operating instructions shall include the following:
a.
principal system and item of equipment.
b.
Start up, proper adjustment, operating, lubrication, and shutdown
procedures.
c.
Safety precautions.
d.
The procedure in the event of equipment failure.
e.
Other items of instruction as recommended by the manufacturer of
each system or item of equipment.
Print or engrave operating instructions and frame under glass or in
approved laminated plastic. Post instructions where directed. For
fade when exposed to sunlight and shall be secured to prevent easy removal
or peeling.
1.9
MANUFACTURER'S NAMEPLATE
Each item of equipment shall have a nameplate bearing the manufacturer's
name, address, model number, and serial number securely affixed in a
conspicuous place; the nameplate of the distributing agent will not be
acceptable.
1.10
FIELD FABRICATED NAMEPLATES
**************************************************************************
NOTE: Use the following paragraph where nameplates
are fabricated to identify specific equipment
designated on the drawings.
**************************************************************************
ASTM D 709. Provide laminated plastic nameplates for each equipment
enclosure, relay, switch, and device; as specified in the technical
sections or as indicated on the drawings. Each nameplate inscription shall
identify the function and, when applicable, the position. Nameplates shall
be melamine plastic, 3 mm (0.125 inch) 0.125 inch thick, white with [black]
[_____] center core. Surface shall be matte finish. Corners shall be
square. Accurately align lettering and engrave into the core. Minimum
size of nameplates shall be 25 by 65 mm (one by 2.5 inches) one by 2.5
inches. Lettering shall be a minimum of 6.35 mm (0.25 inch) 0.25 inch high
normal block style.
1.11
WARNING SIGNS
Provide warning signs for the enclosures of electrical equipment including
substations, pad-mounted transformers, pad-mounted switches, generators,
and switchgear having a nominal rating exceeding 600 volts.
SECTION 16050N
Page 7