required by the Activity.
**************************************************************************
Provide tags of virgin sheet lead, one-piece wraparound strap type, slotted
on one end for attaching the strap. Minimum size of tags shall be 25 mm
wide by 1.2 mm (one inch wide by 3/64 inch) one inch wide by 3/64 inch
thick and a length sufficient for die stamping the identification on one
line and banding around the cable or wire, but not less than 255 mm (10
inches) 10 inches long. Tags shall be die stamped with numbers, letters,
and symbols not less than 6.35 mm (0.25 inch) 0.25 inch high and
approximately 0.38 mm (0.015 inch) 0.015 inch deep in normal block style.
]1.13
ELECTRICAL REQUIREMENTS
Electrical installations shall conform to IEEE C2, NFPA 70, and
requirements specified herein.
1.14
INSTRUCTION TO GOVERNMENT PERSONNEL
Where specified in the technical sections, furnish the services of
competent instructors to give full instruction to designated Government
personnel in the adjustment, operation, and maintenance of the specified
systems and equipment, including pertinent safety requirements as required.
Instructors shall be thoroughly familiar with all parts of the installation
and shall be trained in operating theory as well as practical operation and
maintenance work. Instruction shall be given during the first regular work
week after the equipment or system has been accepted and turned over to the
Government for regular operation. The number of man-days (8 hours per day)
of instruction furnished shall be as specified in the individual section.
[When more than 4 man-days of instruction are specified, use approximately
half of the time for classroom instruction. Use other time for instruction
with equipment or system. When significant changes or modifications in the
equipment or system are made under the terms of the contract, provide
additional instructions to acquaint the operating personnel with the
changes or modifications.]
PART 2
PRODUCTS
2.1
FACTORY APPLIED FINISH
**************************************************************************
NOTE: This paragraph covers only the basic painting
requirements for most electrical equipment. Include
in the section specifying the equipment any special
finishes for high or low temperatures and corrosive
atmospheres. Retain the bracketed statement when
switchgear and other equipment having specific paint
requirements are specified.
**************************************************************************
Electrical equipment shall have factory-applied painting systems which
shall, as a minimum, meet the requirements of NEMA 250 corrosion-resistance
test[ and the additional requirements specified in the technical sections].
PART 3
EXECUTION
3.1
FIELD APPLIED PAINTING
**************************************************************************
SECTION 16050N
Page 9