NOTE: Use and coordinate paint and coating
requirements with Section 09900, PAINTS AND COATINGS
when provided in the job. Use the second bracketed
option when Section 09900 is not provided or when
requirements are beyond what is specified in Section
09900.
**************************************************************************
Paint electrical equipment as required to match finish of adjacent surfaces
or to meet the indicated or specified safety criteria. Painting shall be
as specified in [Section 09900 PAINTS AND COATINGS] [the section specifying
the associated electrical equipment].
3.2
FIELD FABRICATED NAMEPLATE MOUNTING
Provide number, location, and letter designation of nameplates as
indicated. Fasten nameplates to the device with a minimum of two
sheet-metal screws or two rivets.
3.3
WARNING SIGN MOUNTING
Provide the number of signs required to be readable from each accessible
side, but space the signs a maximum of 9 meters (30 feet) 30 feet apart.
3.4
CABLE TAG INSTALLATION
Install cable tags in each manhole, handhole, and vault as specified,
including each splice. [Tag only new wire and cable provided by this
contract.] [Tag new wire and cable provided under this contract and
existing wire and cable which are indicated to have splices and
terminations provided by this contract.] Install cable tags over the
fireproofing, if any, and locate the tags so that they are clearly visible
without disturbing any cabling or wiring in the manholes, handholes, and
vaults.
-- End of Section --
SECTION 16050N
Page 10