the remedies available to the Government under this warranty shall include
repair or replacement of any listed product whose non-compliance is
discovered and made known to the contractor in writing within one year (365
days) after acceptance. Nothing in this warranty shall be construed to
limit any rights or remedies the Government may otherwise have under this
contract, with respect to defects other that Year 2000 performance.
PART 2
PRODUCTS
2.1
Y2K COMPLIANT PRODUCTS
**************************************************************************
NOTE: To ensure that buildings' systems continue to
function beyond Year 2000, the following paragraph
must be included when this section is part of a
construction contract. For more information on Y2K,
see these web sites on the Internet.
http://www.doncio.navy.mil/y2k/year2000.htm, the
Year 2000 homepage of the Department of the Navy
Chief Information Officer (DONCIO);
http://www.itpolicy.gsa.gov/mks/yr2000.legal.htm,
the General Services Administration (GSA) Chief
Information Officer (CIO) homepage for Y2K
procurement, contracting, and legal issues;
http://y2k.lmi.org/gsa/y2kproducts contains
information on vendor product compliance.
**************************************************************************
Provide computer controlled facility components, specified in this section,
that are Year 2000 compliant (Y2K). Computer controlled facility
components refers to software driven technology and embedded microchip
technology. This includes, but in not limited to, telecommunications
systems utilizing microcomputer, minicomputer, or programmable logic
controllers.
2.2
DESIGN OF CARBON DIOXIDE FIRE EXTINGUISHING SYSTEMS
NFPA 12, except as modified herein.
2.2.1
Provide uniform discharge to each raised floor space to achieve a factor of
one pound of carbon dioxide for each [0.28 cubic meters10 cubic feet of
underfloor volume in one minute for underfloor volumes of 56.6 cubic meters
2000 cubic feet or less] [and] [0.34 cubic meter12 cubic feet of underfloor
volume in one minute for underfloor volumes greater than 56.6 cubic meters
2000 cubic feet, except that minimum supply of carbon dioxide shall be 91 kg
200 pounds].
2.2.2
Underfloor Total Flooding Systems Supply
**************************************************************************
NOTE: Designer must ensure that no suffocation
hazard will exist in any rooms with underfloor total
flooding systems or within any space to which the
carbon dioxide might migrate after discharge. Check
with Fire Protection Engineer if in doubt.
SECTION 13961N
Page 10