NOTE: When a single total flooding underfloor
supply is to protect more than one underfloor zone,
clearly indicate the requirements on the drawings.
**************************************************************************
Supply shall include high-pressure storage cylinders, racks, manifolds,
beam scales, and associated equipment. Supply shall consist of carbon
dioxide in [_____] [34 kg] [75 pound] cylinders. Arrange the first [_____]
cylinders for discharge upon activation of the main control, and the
remaining [_____] cylinders for discharge upon activation of the reserve
control.
2.3
PIPE AND FITTINGS
2.3.1
Pipe
Threaded end connections, Schedule 80 or Weight Class XS (Extra Strong),
except that sizes smaller than one inch may be Schedule 40 or Weight Class
STD (Standard).
a.
ASTM A 53, Type E (electric-resistance welded, Grade A or Grade B)
or Type S (seamless, Grade A or Grade B).
b.
ASTM A 106, Grade A or Grade B.
2.3.2
Threaded Fittings
ASME B16.11, except sizes 50 mm 2 inches and smaller may conform to ASME
B16.3, Class 300.
2.3.3
Unions
ASME B16.39, Class 300.
2.4
PIPING ACCESSORIES
2.4.1
Escutcheon Plates
Provide split hinge metal plates for piping entering floors, walls, and
ceilings in exposed spaces. Provide polished stainless steel plates or
chromium plated finish on copper alloy plates in finished spaces. Provide
paint finish on metal plates in unfinished spaces.
2.4.2
Pipe Sleeves
Provide where piping passes entirely through walls, ceilings, roofs, and
floors. Provide sleeves of sufficient length to pass through entire
thickness of walls, ceilings, roofs, and floors. Provide 25 mm one inch
minimum clearance between exterior of piping and interior of sleeve or
core-drilled hole. Firmly pack space with mineral wool insulation and seal
both ends of sleeve or core-drilled hole with plastic waterproof cement
which will dry to a firm but pliable mass, or provide mechanically
adjustable segmented elastomeric seal. In fire walls and fire floors, seal
both ends of sleeves or core-drilled holes with UL listed fill, void, or
cavity material.
SECTION 13961N
Page 11