c.
Include on each drawing the drawing title, number, date, and
paragraph entitled "Identifying Submittals."
d.
Dimension drawings, except diagrams and schematic drawings;
prepare drawings demonstrating interface with other trades to
scale. Shop drawing dimensions shall be the same unit of measure
as indicated on the contract drawings. Identify materials and
products for work shown.
e.
Drawings shall include the nameplate data, size and capacity.
Also include applicable federal, military, industry and technical
society publication references.
1.5.4
Format of SD-03 Product Data and SD-08 Manufacturer's Instruction's
a.
Present product data submittals for each section as a complete,
bound volume. Include table of contents, listing page and catalog
item numbers for product data.
b.
Indicate, by prominent notation, each product which is being
submitted; indicate specification section number and paragraph
number to which it pertains.
c.
Supplement product data with material prepared for project to
satisfy submittal requirements for which product data does not
exist. Identify this material as developed specifically for
project, with information and format as required for submission of
SD-07 Certificates..
d.
Provide product data in metric dimensions. Where product data are
included in preprinted catalogs with English units only, submit
metric dimensions on separate sheet.
e.
Product data shall include the manufacturer's name, trade name,
place of manufacture, and catalog model or number. Submittals
shall also include applicable federal, military, industry and
technical society publication references. Should manufacturer's
data require supplemental information for clarification, the
supplemental information shall be submitted as specified for SD-07
Certificates.
f.
Where equipment or materials are specified to conform to industry
such as American National Standards Institute (ANSI), ASTM
International (ASTM), National Electrical Manufacturer's
Association (NEMA), Underwriters Laboratories (UL), and
Association of Edison Illuminating Companies (AEIC), submit proof
of such compliance. The label or listing by the specified
organization will be acceptable evidence of compliance. In lieu
of the label or listing, submit a certificate from an independent
testing organization, competent to perform testing, and approved
by the Contracting Officer. The certificate shall state that the
item has been tested in accordance with the specified
organization's test methods and that the item complies with the
specified organization's reference standard.
g.
Submit manufacturer's instruction prior to installation.
SECTION 01330
Page 15