b. A waveform with an 8 microsecond rise time, a 20 microsecond
waveform, a peak voltage of 1000 volts and a peak current of 500
amperes.
1.3
DELIVERY OF TECHNICAL DATA
**************************************************************************
NOTE: The wireline DTS will be used with either the
electronic security systems (ESS), small intrusion
detection system (IDS), closed circuit television
(UMCS), the power monitoring system, or the
supervisory control and data acquisition (SCADA)
system. The designer will select the system and
supply the correct section title where appropriate:
Section 13702N BASIC INTRUSION DETECTION SYSTEMS
(IDS), Section 13703N COMMERCIAL INTRUSION DETECTION
SYSTEMS (IDS), Section 13720A ELECTRONIC SECURITY
SYSTEM, Section 13721A SMALL INTRUSION DETECTION
SYSTEM, or Section 16751A CLOSED CIRCUIT TELEVISION
SYSTEMS.
**************************************************************************
All items of technical data which are specifically identified in this
specification will be delivered strictly in accordance with the CONTRACT
CLAUSES, SPECIAL CONTRACT REQUIREMENTS, Section 01330 SUBMITTAL PROCEDURES
and the Contract Data Requirements List, DD Form 1423, which is attached to
and made a part of this contract. Technical data submitted shall be
coordinated with the requirements of Section [_____]. All data delivered
shall be identified by reference to the particular specification paragraph
against which it is furnished [_____] hard copies and [_____] electronic
copies (CD-ROM or DVD-R) of the Technical Data Package(s) shall be
submitted.
1.3.1
Group I Technical Data Package
1.3.1.1
System Drawings
The data package shall include the following:
a. Data Transmission system block diagram.
c. MODEMS or line drivers or both, physical layout and schematics.
e. Details of interconnection with served system components.
f. Details of surge protection device installation.
g. Details of cable splicing and connector installation.
h. Details of underground, aerial, and messenger cable installation on
poles, cable entrance to building.
SECTION 16792A
Page 7