insulation, type of filling compound, core lay-ups, color code, sheath
design (shielding materials, single or double jackets, and jacket
thickness), and screened or non-screened core.
2.2.3
Aerial Cable
Aerial cable as specified in ICEA S-84-608 covers mechanical and electrical
requirements for filled, polyolefin insulated, copper conductor
telecommunications cable. It provides alternative choices for type of
insulation, type of filling compound, core lay-ups, color code, sheath
design (shielding materials, single or double jackets, and jacket
thickness), and screened or non-screened core.
2.2.4
Direct Burial Cable
Direct burial cable as specified in RUS Bull 345-67 covers mechanical and
electrical requirements for filled, polyolefin insulated, copper conductor.
It provides alternative choices for type of insulation, type of armor
jacket, filling compound, core lay-ups, color code, sheath design
(shielding materials, single or double jackets, and jacket thickness), and
screened or non-screened core.
2.2.5
Interior Cable
Interior cable, as specified in NFPA 70 covers mechanical and electrical
requirements for filled, polyolefin insulated copper conductor
insulation, type of jacket, filling compound, core lay-ups, color code,
sheath design (shielding materials, single or double jackets, and jacket
thickness), and screened or non-screened core. All interior cables'
insulation and jacketing material shall not contain any poly vinyl chloride
(PVC) compounds.
2.3
RACEWAY SYSTEMS
Raceway systems as specified in Section 16402 INTERIOR DISTRIBUTION SYSTEM
and Section 16375A ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND and as shown
shall be furnished and installed.
2.4
ENCLOSURES
**************************************************************************
NOTE: The designer will show the specific type of
enclosure required on the drawings.
**************************************************************************
Enclosures shall conform to the requirements of NEMA 250 for the types
specified. Finish color shall be the manufacturer's standard, unless
otherwise indicated. Damaged surfaces shall be repaired and refinished
using original type finish. The Contractor shall provide metallic
enclosures to house the wireline DTS equipment. The enclosures shall be as
specified or shown.
2.4.1
Interior
Enclosures to house wireline DTS equipment in an interior environment shall
meet the requirements of NEMA 250, Type 12.