b. The Government shall be granted a nonexclusive, fully paid perpetual
license to use software provided. The Government receives no title or
ownership rights to such Software.
c. Software maintenance that is provided to any or all other customers
without charge shall be provided to the Government at no additional cost to
the Government.
2.1.9
Equipment Design for Wet Areas
All equipment that will be installed in wet areas shall be designed and
constructed to withstand the UL 1069 Water Spray Test.
2.2
NC SUBSYSTEMS
2.2.1
Patient Stations
a.
Flush mount units.
b. Three (3) types of patient stations as listed below. Each type shall
have the required common characteristics, plus the defined additional
characteristics.
Type 1: Common characteristics.
Type 2: Common characteristics plus call cord receptacles.
Type 3: Common characteristics plus tamper proof construction.
c.
Common characteristic for all types of patient stations.
(1) A call push button switch that is clearly labeled with the term
"CALL".
(2) A red color emergency push button call switch that is permanently
labeled as an Emergency call switch on or directly adjacent to the call
switch.
(3) A call cancel push button switch that is clearly labeled
"CANCEL". Alternatively, the cancel function may be a toggle of the call
switch.
(4) Full-duplex intercom as specified herein, including microphone
and speaker.
(5) Circuitry for interface with a patient TV set, including
automatic muting of TV audio during call voice intercom periods.
(6) Circuitry for interface with a bed SideCom for nurse call, TV
operation and sound, and bed exit alarm call, via the interconnected bed
interface outlet station.
(7) Circuitry for connection of cord sets that are plugged into the
interconnected remote cord sets outlet station simultaneous with the
connection of a bed SideCom that is plugged into the interconnected bed
interface outlet station.
(8) An LED call assurance indicator lamp.
d.
Additional Type 2 patient station characteristics.
SECTION 16731A
Page 40