2.2.6
Emergency Pull Cord Stations
a.
Flush mount units.
b. An emergency call switch that is activated by pulling a nylon cord
attached to the switch. The cord shall have a pendant attached to the end
of the cord, and length extended to within 50 mm 2 inches of the floor.
The term "PULL FOR HELP" shall be located directly adjacent to the call
switch.
c. A call cancel push button switch that is clearly labeled either
"CANCEL" or "RESET". Alternatively, the cancel function may be a toggle of
the emergency call switch. For stations installed in showers or baths that
are located in the same room as a toilet, it is acceptable to have the
cancel function for the shower/bath station operated from the adjacent
emergency pull cord toilet station.
d.
An LED call assurance indicator.
e. Stations installed in wet areas shall be water resistant and shall
comply with water spray exposure requirements of UL 1069.
f.
Waterproof gaskets for stations installed in wet areas.
2.2.7
Emergency Push Button Stations
a.
Flush mount units.
b. A red color emergency push button call switch that is permanently
labeled as an Emergency call switch on or directly adjacent to the call
switch.
c. A call cancel push button switch that is clearly labeled "CANCEL".
Alternatively, the cancel function may be a toggle of the emergency call
switch.
d.
An LED call assurance indicator.
e. Stations installed in wet areas shall be water resistant and shall
comply with water spray exposure requirements of UL 1069.
f.
Waterproof gaskets for stations installed in wet areas.
2.2.8
Code Blue Stations
a. Flush mount units in independent enclosures. Code blue stations that
are physically part of any other call station shall not be acceptable.
b. A blue color code blue push button call switch with the term "CODE" or
"CODE BLUE" located on or directly adjacent to the push button.
c. A call cancel push button switch that is clearly labeled "CANCEL".
Alternatively, the cancel function may be a toggle of the code blue call
switch.
d.
An LED call assurance indicator.
SECTION 16731A