within the required response time.
c. Repair of a major malfunction shall be accomplished within 8 hours of
the reported failure. The occurrence of any of the following events shall
constitute a major malfunction:
(1) Complete failure of any Major Functional Component of the system,
including:
Nurse Call (NC) Subsystems
Central Code Annunciator Stations
Call Logging Workstation
Maintenance Workstation
Local Area Network (LAN)
System Servers
Call Logging Server
Information System Server
Radio Page Server
Wireless Telephone Server
(2) Failure of a power supply, exclusive of commercial ac power feed.
(3) Failure of 20% or more of all stations in any one NC Subsystem to
function as specified.
(4) Failure of any NC Subsystem master station, code blue or infant
code blue station, or emergency station.
d. Repair of minor malfunctions shall be completed within 48 hours of the
reported failure. A minor malfunction is any failure that does not
constitute a major malfunction.
PART 2
PRODUCTS
2.1
MATERIAL AND EQUIPMENT
**************************************************************************
NOTE: Delete the specifications for any Product
that is not part of the system design. Modify the
specifications for any Product as required to
conform to the specified performance requirements.
**************************************************************************
2.1.1
New Products
All products shall be new and free of defects.
2.1.2
Unspecified Products
If the provided system requires additional products that are not specified
or indicated on the drawings, in order to satisfy the specified performance
requirements for the system, then these additional component products shall
be provided at no additional cost to the Government.
2.1.3
Product Modifications
Modification of products that nullifies the UL listing or other agency
approval is not permitted.