1.2
GENERAL REQUIREMENTS
**************************************************************************
NOTE: Select the features and fill in blanks with
selections appropriate for the design condition and
in accordance with guidance contained in TM
5-811-1/AFM 88-9 Chapter 1.
**************************************************************************
1.2.1
Terminology
Terminology used in this specification is as defined in ANSI C42.100.
1.2.2
System Description
The system shall be configured as specified, and shall include structures,
incoming and outgoing lines, transformers, regulators, fuses, circuit
breakers, switches, switchgear, and appurtenances to provide a fully
functional system.
1.2.3
Service Conditions
**************************************************************************
NOTE: See TM 5-811-1/AFM 88-9 Chapter 1 for
guidance regarding service conditions. Retain or
add the required conditions.
Provide seismic requirements, if a Government
designer (either Corps office or A/E) is the
Engineer of Record, and show on the drawings.
Delete the bracketed phrase if seismic details are
not included. Sections 13080, 15070A and 16070A,
properly edited, must be included in the contract
documents.
**************************************************************************
Items provided under this section shall be specifically suitable for the
following service conditions. Seismic details shall conform to Sections
13080 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT, 15070A SEISMIC
PROTECTION FOR MECHANICAL EQUIPMENT, and 16070A SEISMIC PROTECTION FOR
ELECTRICAL EQUIPMENT [as indicated].
a.
Fungus Control [_____]
b.
Altitude [_____] m feet
c.
Ambient Temperature [_____] degrees C degrees F
d.
e.
Ventilation [_____] cubic meters/sec cfm
f.
Seismic Parameters [_____]
g.
Humidity Control [_____]
h.
Corrosive Areas [_____]
SECTION 16311A