Device/Condition/
What/Where/Size
NFPA 99
NFPA 110
NFPA 110
Low fuel level
Main tank, 3 hr
VA/AA
AA
AAO
remaining
Overcrank
Failure to start
VA/AA
AA
AAO
Overspeed
VA/AA
AA
AAO
Pre-high temperature
Jacket water/
AA
cylinder
Control switch not in
AA
AUTO
Common alarm contacts
X
X
for local & remote
common alarm
Audible alarm silencing
X
O
switch
Air shutdown damper
When used
AA
AAO
Common fault alarm
AA
X
-
Required
SD
-
Shut Down
CP
-
On Control Panel
VA
-
Visual Alarm
AA
-
Audible Alarm
O
-
Optional]
2.17
Devices, wiring, remote panels, local panels, etc., shall be provided and
installed as a complete system to automatically activate the appropriate
signals and initiate the appropriate actions.
2.17.1
Controls
**************************************************************************
NOTE: Delete the remote control (control room)
panel if the application is not a prime power
application. Provide plan and elevation drawings of
the remote control panels for prime power
applications, depicting specific devices,
instrument, and meters, including layouts.
indication may be added if required (Not available
for standard molded-case breakers. Use only for
Edit the table to include all required devices.
Delete all columns except the first column and the
appropriate reference columns (always delete "MFG
Offering" column).