A local alarm panel shall be provided with the following shutdown and alarm
functions [as indicated] [in accordance with NFPA [99] [110 level [1] [2]]
and including the listed Corps of Engineers requirements, mounted either on
Device/
What/Where/Size
NFPA 99
NFPA 110
NFPA 110
Corps of
Condition/
Level 1
Level 2
Engrs
Function
Required
Shutdowns
W/Alarms
High engine
Automatic/
SD/CP VA
SD/CP VA
SD/CP VA
SD VA
temperature
jacket
water/
cylinder
Low lube-oil
Automatic/
SD/CP VA
SD/CP VA
SD/CP VA
SD VA
pressure
pressure/
level
Overspeed
(110% (+ 2%)
SD/CP VA
SD/CP VA
SD/CP VA
SD VA
shutdown $
of rated
alarm
speed
Overcrank
Automatic/
SD/CP VA
SD/CP VA
SD/CP VA
failure
Failure to
to start
to start
Air shutdown
When used
SD/CP VA
SD/CP VA
damper
(200-600kW)
Day tank
Automatic/Day
SD/OPA
overfill
Tank/Level
(Pump)
limit
indication &
transfer pump
shutdown
(95% volume)
Red emergency
Manual Switch
SD/CP VA
SD/CP VA
SD VA
stop switch
Failure to
Corps of Engrs.
crank
Required
[Day tank]
Corps of Engrs.
[Integral Main
Required
Fuel Tank]
low fuel
SECTION 16264A
Page 47