Device/
What/Where/Size
NFPA 99
NFPA 110
NFPA 110
Corps of
Condition/
Level 1
Level 2
Engrs
Function
Required
limit Device/
Condition/
indication
(70% volume
remaining)
Alarms
Low lube-oil
Pressure/
CP VA
CP VA
CP VAO
CP VA
pressure
level
Low fuel
Main tank,
VA/AA
CP VA
CP VAO
level
3 hours
remaining
High fuel
Integral Main
CP VA
level
Fuel Storage
Tank
95% Volume
Low coolant
Jacket water
CP/VA
CP VA
CP VA
Pre-high
Jacket water/
CP VA
CP VA
CP VAO
CP VA
temperature
cylinder
Pre-low
CP VA
CP VA
lube-oil
pressure
High battery
CP VA
CP VAO
voltage
Low battery
CP VA
CP VAO
voltage
Battery
AC supply not
CP VA
CP VAO
charger
available
AC failure
Control
CP VA
CP VAO
switch not
in AUTO
Low starting
CP VA
CP VAO
air pressure
Low starting
CP VA
CP VAO
hydraulic
pressure
SD
-
Shut Down
CP
-
On Control Panel
VA
-
Visual Alarm
AA
-
Audible Alarm
O
-
Optional]
SECTION 16264A