Device/Condition/
Corps Requirement
NFPA 110
NFPA 110
MFG
Function
Level 1
Level 2
Offering
AC volts (generator),
CP
CP/STD
3-phase
AC amps (generator),
CP
CP/STD
3-phase
CP
CP/STD
Phase selector switches
CP
CP/STD
(amps & volts)
Watts/kW
CP/VA-O
Voltage Regulator
Adjustment
CP
CP - On Control Panel
VA - Visual Alarm
AA - Audible Alarm
O - Optional
STD - Manufacturers Standard Offering
2.18
PANELS
**************************************************************************
NOTE: Panels, except the remote panel, can be
combined into a single panel paragraph.
Provide a panel-mounting location and detail for
panels not mounted on the generator set base. The
designer may elect other locations such as adjacent
to engine generator set; in the generator enclosure;
or in or on the switchgear enclosure.
Provide panel nameplate and instrument nameplate
unique identifiers or user preferred identifiers.
Provide sizes, materials, and attachment preferences.
Delete either the "standard panel" or "electronic
panel".
**************************************************************************
Each panel shall be of the type necessary to provide specified functions.
Panels shall be mounted [on the engine generator set base by
vibration/shock absorbing type mountings] [as shown]. Instruments shall be
mounted flush or semiflush. Convenient access to the back of instruments
shall be provided to facilitate maintenance. Instruments shall be
calibrated using recognized industry calibration standards. Each panel
shall be provided with a panel identification plate which clearly
identifies the panel function as indicated. Each instrument and device on
the panel shall be provided with a plate which clearly identifies the
device and its function as indicated. Panels except the remote alarm panel
can be combined into a single panel.
2.18.1
Enclosures
**************************************************************************
SECTION 16264A
Page 53