smaller than 200 kW, KWh, kVAR, power factor meters
and reverse power indication may be added as
required.
The following instruments may be added as required.
Indicating VAR meter. Power-factor meter,
indicating. (Specify one of these. They are
normally used only for prime applications, however
can be specified for standby units as required.)
Indicating wattmeter. (Normally used only for prime
applications, however can be specified for standby
units as required.)
Totalizing Kilowatt-hour meter with 15 or 30 minute
demand register. (Normally used only for prime
applications, however can be specified for standby
units as required.)
Recording Kilowatt-hour/demand meter. (Normally
used only for prime applications, however can be
specified for standby units as required.)
The 15-minute demand register is preferred to the
30-minute register in most cases, because it permits
more accurate timing of facility peak load
occurrence.
Delete Frequency and Volt meters if a Synchronizing
Panel is provided.
**************************************************************************
A local panel shall be provided with devices [as indicated] [in accordance
with NFPA 110 level [1] [2]] [and as follows] mounted [either on or
adjacent to the engine generator set] [as indicated]. A remote control
panel shall be provided [with devices as indicated] [fully redundant to the
Device/Condition/
Corps Requirement
NFPA 110
NFPA 110
MFG
Function
Level 1
Level 2
Offering
Genset Status & Metering
Genset supplying load
CP VA
CP VAO
CP VAO
System ready
CP/STD
Engine oil pressure
CP
CP/STD
Engine coolant temperature
CP
CP/STD
CP
CP/STD
Engine run hours
CP
CP/STD
Pyrometer display
CP
w/selector switch