SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE ARP892
SAE J1995
(1995) Engine Power Test Code - Spark
Ignition and Compression Ignition - Gross
Power Rating
SAE J537
(2000) Storage Batteries
UNDERWRITERS LABORATORIES (UL)
UL 1236
(2002) Battery Chargers for Charging
Engine-Starter Batteries
1.2
SYSTEM DESCRIPTION
1.2.1
General Requirements
[The] [Each] engine shall be provided and installed complete and totally
functional, with all necessary ancillary equipment including, but not
engine rating shall be in accordance with SAE J1995. The [diesel] [natural
gas fueled] engine pump drives shall be complete units with all components,
assembly shall have the capabilities required, for proper operation with
the pump specified under Section 15131A VERTICAL PUMPS, AXIAL-FLOW AND
MIXED-FLOW IMPELLER-TYPE and the speed reducer specified in Section 15005A
SPEED REDUCERS FOR STORM WATER PUMPS.
1.2.2
Performance Requirements
**************************************************************************
NOTE: The designer should specify the service
requirements for the pump drive: Continuous,
Standby, or Emergency. The designer should furnish
pump manufacturer's data including pump curves and
plans unless this specification is used in
conjunction with pump specification UFGS-15131A as a
package. The selection of the engine speed should
follow the guidance given in EM 1110-2-3105. Rated
capacity should be based on the pump manufacturer's
recommendation.
**************************************************************************
Service Requirements:
[Continuous][Standby][Emergency]
Rated Capacity:
[110 percent maximum kW (HP)
required from the pump curves at
specified speed plus power required
by the accessories]
Overload Capacity:
[110 percent rated capacity for
2 hr in 24 consecutive hrs]
Maximum Speed:
[_____][900][1,200][1,800] RPM
[Characteristics of the pump load for the engine drive are
SECTION 15133A