Spare Parts
Spare parts data as specified.
AFFF System[; G][; G, [_____]]
A copy of the proposed diagrams and instructions for the overall
Installer's Qualifications[; G][; G, [_____]]
Data approved, prior to submittal of any other data or drawings,
to substantiate that the proposed installer is regularly engaged
in the installation of the type and complexity of fire protection
system included in this project. Data shall identify the location
of three systems recently installed by the proposed installer
which are comparable to the system specified. Contractor shall
certify that each system has performed satisfactorily, in the
manner intended, for a period of not less than 6 months.
Post-discharge Test Requirements[; G][; G, [_____]]
Details of method proposed for required tests at Final
Acceptance, including step-by-step test procedures; list of
equipment to be used; names, titles, and affiliations and
qualifications of personnel who will participate in the tests;
methods for protecting the facility and equipment during testing;
means for containing the AFFF solution during discharge tests; and
proposed means for disposal. Test plan shall include a drawing
showing proposed number and arrangement of fire hoses and nozzles
proposed for use in testing foam proportioners. Blank forms the
Contractor plans to use to record test results shall be included.
SD-06 Test Reports
Tests[; G][; G, [_____]]
Reports for tests, as follows:
a. Reports as outlined in NFPA 13 documenting results of
b. Trip tests of [alarm check] [and] [automatic water control]
valves.
c. Test report of AFFF concentrate proportioning system.
Report shall include all pressure readings and settings of pumps,
pressure sustaining valves, relief valves and similar system
components. Report shall include conductivity readings for foam
samples taken from each AFFF proportioner. Report shall be signed
by the factory-trained technical representative employed by the
AFFF concentrate manufacturer.
d. Test report of the foam system control panel and initiating
and indicating devices. Report shall include a unique identifier
for each device with an indication of test results. Report shall
be signed by the factory-trained technician employed by the
control panel manufacturer.
SECTION 13955A
Page 10