1.8
SPARE PARTS
The Contractor shall submit spare parts data for each different item of
material and equipment specified. The data shall include a complete list
of parts and supplies, with current unit prices and source of supply, and a
list of parts recommended by the manufacturer to be replaced after 1 year
and 3 years of service. A list of special tools and test equipment
required for maintenance and testing of the products supplied by the
Contractor shall be included.
PART 2
PRODUCTS
2.1
STANDARD PRODUCTS
Materials and equipment shall be standard products of a manufacturer
regularly engaged in the manufacture of such products and shall essentially
duplicate items that have been in satisfactory use for at least 2 years
prior to bid opening.
2.2
REQUIREMENTS FOR FIRE PROTECTION SERVICE
All equipment and material shall have been tested by Underwriters
Laboratories, and listed in UL Fire Prot Dir or approved by Factory Mutual
and listed in FM P7825a. Where the terms "listed" or "approved" appear in
this specification, such shall mean listed in UL Fire Prot Dir or FM P7825a.
The omission of these terms under the description of any item of equipment
described shall not be construed as waiving this requirement.
2.3
PRESSURE RATINGS
Valves, fittings, couplings, proportioners, alarm switches, strainers, and
similar devices shall be rated for the maximum working pressures that can
be experienced in the system, but in no case less than 1200 kPa 175 psi.
2.4
NAMEPLATES
Major components of equipment shall have the manufacturer's name, address,
type or style, model or serial number, and catalog number on a plate
permanently affixed to the item of equipment.
2.5
**************************************************************************
NOTE: Assure that this provision is coordinated
with drawings and other specification sections.
**************************************************************************
Pipe shall be ductile iron pipe conforming to AWWA C151, working pressure
not less than 1034 kPa 150 psi, with cement-mortar lining conforming to
AWWA C104 for piping under the building and to a point 1.5 m 5 feet outside
the building walls. Fittings shall be ductile iron conforming to AWWA C110.
Piping more than 1.5 m 5 feet outside the building walls shall be
[outside-coated cement-lined ductile iron pipe] [provided under SECTION
02510A WATER DISTRIBUTION SYSTEM].
SECTION 13955A
Page 13