District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control
approval.] [information only. When used, a designation following the "G"
designation identifies the office that will review the submittal for the
Government.] The following shall be submitted in accordance with Section
01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
AFFF System[; G][; G, [_____]]
NFPA 13; drawings shall be 841 x 594 mm 30 x 42 inches. Drawings
shall include plan and elevation views which establish that the
equipment will fit the allotted spaces with clearance for
installation and maintenance. Each set of drawings shall include
the following:
a. A descriptive index with drawings listed in sequence by
number. A legend sheet identifying device symbols, nomenclature,
and conventions used in the package.
b. Floor plans drawn to a scale not less than 1:100 1/8 inch
equals 1 foot clearly showing locations of devices, equipment,
risers, electrical power connections, flame detector viewing
areas, areas covered by each nozzle, and other details required to
clearly describe the proposed arrangement.
c. Piping plan for each individual sprinkler system and each
nozzle system. Sprinklers, nozzles and associated piping shall be
shown. Abbreviated presentation forms will not be accepted. Each
type of fitting used and the locations of bushings, reducing
couplings, and welded joints shall be identified. A separate plan
shall be provided for each overhead sprinkler system and each
nozzle system.
d. Piping plan and isometric drawing of the AFFF concentrate
system and details of all associated pumps, valves, fittings, and
other components. Drawing shall indicate all operational features
including, but not limited to, settings for pump start/stop,
relief valve open/close, pressure sustaining valve open/close.
e. Actual center-to-center dimensions between sprinklers on
branch lines and between branch lines; from end sprinklers to
adjacent walls; from walls to branch lines; and from sprinkler
feed mains, crossmains and branchlines to finished floor and roof
or ceiling.
SECTION 13955A
Page 8