e.
Videotapes of tests specified to be recorded.
SD-07 Certificates
Materials and Equipment[; G][; G, [_____]]
Certificates from manufacturers to substantiate that components,
equipment and material proposed for installation and use meet
requirements as specified, concurrent with submittal of
manufacturer's catalog data of equipment proposed for
installation. Certificates shall be on a form for this purpose or
on official letterhead of the manufacturer with specified
information stated as required. Certificate shall be signed by an
officer of the corporation. Certificates shall be provided for
the following:
a. AFFF concentrate. Certification that AFFF concentrate
proposed for use has been tested and is in compliance with
b. AFFF concentrate control valve. Certification that the
valve is designed and, constructed as specified and will function
as intended.
c. AFFF proportioning system. Certification that the foam
proportioning system complies with contract specifications and
manufacturer's recommendations.
d. Control panel. Certification that the control panel
releasing module is electrically compatible with the
electrically-actuated automatic water control valve.
SD-10 Operation and Maintenance Data
AFFF System[; G][; G, [_____]]
[Six] [_____] manuals in loose-leaf binder format and grouped by
technical sections consisting of manufacturer's brochures,
schematics, printed instructions, general operating procedures,
and safety precautions. Manuals shall include a narrative
description of the sequence or sequences of operation of the
overall fire protection system and a separate description for each
major subsystem. Information to be provided shall include
specific start/stop settings for pumps, open/close settings for
all adjustable valves (including pressure sustaining and relief
valves) shall be included. The manuals shall list routine
maintenance procedures, possible breakdowns, and repairs, and
troubleshooting guide. The manuals shall include conduit layout,
equipment layout, and simplified wiring and control diagrams for
the system as installed. The manuals shall include procedures and
instructions pertaining to frequency of preventive maintenance,
inspection, adjustment, lubrication and cleaning necessary to
1.3
AFFF SYSTEM
The system shall consist of an automatic [wet-pipe] [preaction] [deluge]
foam-water fire protection system and shall be provided for the areas
SECTION 13955A
Page 11