raceway cover.
Magnet held base covers will not be accepted.
2.2.7
Leveling Glides
The system shall provide precise alignment of adjacent panels and spine
walls and shall include leveling glides to compensate for uneven floors.
On panel-to-panel products, each panel shall have 2 leveling glides. On
panel-to-post products each connector shall contain a leveling glide. On
stacking panel frames each vertical panel assembly shall have two leveling
guides. A minimum 20 mm 3/4 inch adjustment range is required for all
systems.
2.2.8
Panel and Spine Wall Connection System
**************************************************************************
NOTE: Delete connection of 2 panels for setting the
panels at any angle if not required. This
connection limits sources.
**************************************************************************
The panel and spine wall system shall have connectors which accommodate a
variety of configurations as shown on the drawings. A straight line
connection of 2 panels (180 degrees), corner connection of 2 panels (90
degrees), T connection of 3 panels (90 degrees), cross connection of 4
panels (all 90 degrees), and a connection of 2 panels for setting the
panels at any angle. The connector system shall provide tight connections
with continuous visual and acoustical seals. All two-way and T connections
should have plastic, painted metal, fabric or wood finish to match system.
The connector system shall allow removal of a single panel or spine wall
within a typical workstation configuration, without requiring disassembly
of the workstation or removal of adjacent panels or spine walls. The
connector system shall provide for connection of panels or spine walls of
similar or dissimilar heights. When stacking panel frames are specified,
taller panel assemblies of adjacent dissimilar height panel assemblies
shall be provided with trim pieces to finish the exposed edge. Right angle
(90 degree) connections between panels shall not interfere with the
capability to hang work surfaces and other components on any adjacent
panel. The connector system shall provide, as required, for the
continuation of electrical and communications wiring within workstations
and from workstation to workstation. Filler posts shall be level with the
panel or spine wall top rail.
2.2.9
Wall Mounted Panels
Wall-mount accessories shall be used when it is necessary to attach panels
or vertical panel-frame assemblies to the building walls. Wall panels
shall have structural support as required.
2.2.10
Glazed Panels
Glazed panel inserts shall be comprised of tempered glass in accordance
with ANSI Z97.1. Acrylic glazing will not be accepted.
2.2.11
Door Panels
Door panels shall have a rigid metal frame with rails, a threshold, and a
[wood] [laminate] [safety glazed] [_____] clad door adaptable to either
hand swing. Door panels shall be of a dimension that will allow for a 810
mm 32 inch clear opening. Door panels shall include connectors, hinges,
SECTION 12705
Page 15