Backing
ASTM F 2034
(2003) Sheet Linoleum Floor Covering
ASTM F 2169
(2002) Resilient Stair Treads
ASTM F 2170
Concrete Floor Slabs in situ Probes
ASTM F 2195
(2003) Linoleum Floor Tile
ASTM F 710
(2003) Standard Practice for Preparing
Concrete Floors to Receive Resilient
Flooring
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule #1168
(2003) Adhesive and Sealant Applications
1.2
**************************************************************************
NOTE: Choice of critical radiant flux level as it
applies to building type and area of application
will be made in accordance with the latest edition
of UFC 3-600-01 and NFPA 101. Wherever the use of
Class II (0.22) watts finish is required, Class I
(0.45) watts will be permitted. Critical radiant
flux will be a minimum average of 0.45 watts when
used in corridors in bachelor enlisted quarters,
bachelor officer quarters, hospital, child care
centers, temporary lodging facilities, and new
construction detention and correctional facilities.
Generally the critical radiant flux will be a
minimum of 0.22 for corridors of other type
facilities. Where an approved automatic sprinkler
system is installed, Class II interior floor finish
may be used where Class I floor finish is required,
and where Class II is required, no critical radiant
flux rating is required. Omit paragraph if not
applicable.
**************************************************************************
Flooring in corridors and exits shall have a minimum average critical
radiant flux of [0.22] [0.45] watts per square centimeter when tested in
accordance with ASTM E 648.
1.3
SUBMITTALS
**************************************************************************
NOTE: Submittals must be limited to those necessary
for adequate quality control. The importance of an
item in the project should be one of the primary
factors in determining if a submittal for the item
should be required.
A "G" following a submittal item indicates that the
submittal requires Government approval. Some
submittals are already marked with a "G". Only
SECTION 09650
Page 5