refrigerants to the atmosphere in accordance with the Clean Air Act
Amendment of 1990.] [Recover all refrigerants prior to removing air
conditioning equipment and dispose of in accordance with the paragraph
entitled "Disposal of Ozone Depleting Substance (ODS)."] [Turn in salvaged
Class I ODS refrigerants as specified in paragraph, "Salvaged Materials and
Equipment."]
3.1.14
Cylinders and Canisters
Remove all fire suppression system cylinders and canisters and dispose of
in accordance with the paragraph entitled "Disposal of Ozone Depleting
Substance (ODS)."
3.1.15
Locksets on Swinging Doors
**************************************************************************
NOTE: Use this paragraph when demolition includes
removal and disposal of hinged or pivoted swinging
doors. (This is a security measure.)
**************************************************************************
The Contractor shall remove all locksets from all swinging doors indicated
to be removed and disposed of. Deliver the locksets and related items to a
designated location for receipt by the Contracting Officer after removal.
3.1.16
Mechanical Equipment and Fixtures
**************************************************************************
NOTE: Delete, revise, or add to the text to cover
the project requirements. Materials and equipment
scheduled for salvage should be noted on the
drawings.
**************************************************************************
Disconnect mechanical hardware at the nearest connection to existing
services to remain, unless otherwise noted. Mechanical equipment and
fixtures must be disconnected at fittings. Remove service valves attached
to the unit. Salvage each item of equipment and fixtures as a whole unit;
listed, indexed, tagged, and stored. Salvage each unit with its normal
including motors and machines, to a designated [on station] storage area as
directed by the Contracting Officer. Do not remove equipment until
approved.
3.1.16.1
Preparation for Storage
Remove water, dirt, dust, and foreign matter from units; tanks, piping and
fixtures shall be drained; interiors, if previously used to store
flammable, explosive, or other dangerous liquids, must be steam cleaned.
Seal openings with caps, plates, or plugs. Secure motors attached by
proper oil or grease.
3.1.16.2
Piping
Disconnect piping at unions, flanges and valves, and fittings as required
to reduce the pipe into straight lengths for practical storage. Store
SECTION 02220
Page 16