1.4.2.5
LAN
**************************************************************************
NOTE: If the NCAV System is to be interfaced with a
networked NCTV System in the same medical facility,
include item "d." below.
**************************************************************************
a. A dedicated NCAV System LAN shall connect all Major Functional
Components of the system into an integrated network for system wide data
b.
The NCAV System LAN shall be interfaced with the medical facility
Information Systems LAN through the Information System Server and the Call
Logging Server for functions as specified in this Section.
c.
LAN equipment shall be located as required by the system application
design.
d.
Integrate the NCAV System LAN with the NCTV System LAN for data
Annunciator Station [, Call Logging,][and Radio Page].
1.4.2.6
Central Code Annunciator Stations
**************************************************************************
NOTE: As indicated below, there are two
annunciation points for Infant Code Blue alarms: on
the Master Code Annunciator Station, and on the
Infant Code Blue Annunciator Station.
**************************************************************************
a. A Master Code Annunciation Station for the central annunciation of all
Code Blue and all Infant Code Blue calls from all NC Subsystems equipped
with code blue stations or infant code blue stations [, and all NCTV NC
Subsystems that are equipped with code blue stations]. The Master Code
Annunciator Station shall be located at a central 24x7 staffed location as
indicated on the telecommunications drawings.
b. An Infant Code Annunciation Station for the central annunciation of all
Infant Code Blue calls from NC Subsystems equipped with infant code blue
stations. The Infant Code Blue Annunciator Station shall be located at a
24x7 staffed Neonatal Intensive Care Unit location as indicated on the
telecommunications drawings.
1.4.2.7
Call Logging Workstation
A computer workstation for the central processing and generation of call
data statistical reports from all NC Subsystems. The workstation shall be
located as indicated on the telecommunications drawings.
1.4.2.8
Maintenance Workstation
A computer workstation for remote monitoring and troubleshooting of
failures throughout the system, and for down loading and installation of
software upgrades from the Manufacturer. The Maintenance Workstation shall
be located as indicated on the telecommunications drawings.
SECTION 16731A
Page 19