The system shall provide the capability, interface protocols, and
and systems:
(1)
Control of Overbed Lights
Interface with the low voltage controller for the overbed lights at each
patient bed shall allow remote on/off control of the overbed reading light
from a single push button toggle switch on the pillow speaker cord set and
on the bed SideCom [, and remote on/off control of the overbed indirect
room light from a single push button toggle switch on the pillow speaker
cord set and on the bed SideCom].
**************************************************************************
NOTE: If patient bedside personal TV Sets (the
small size TV Sets which hang on an arm that is
mounted on the headwall adjacent to the patient bed)
are used, then delete the following paragraph "(2)"
and all subsequent references to this TV interface
function.
**************************************************************************
(2)
Patient TV Control and Sound
Interface with the TV Set in each patient room shall allow TV Set control
and remote sound from a pillow speaker cord set and a bed SideCom.
(3)
Bed SideCom Functions and Bed Exit Safety Alarms
Interface with the patient bed SideCom, via the bed communications cable,
shall allow initiation of a routine patient call, TV Set controls and
remote sound, and Bed Exit System safety alarm calls from the SideCom.
**************************************************************************
NOTE: If Infant Protection Systems are NOT provided
by the project or the medical facility, then deleted
the following paragraph "(4)" and all subsequent
references to this interface function.
**************************************************************************
(4)
Infant Protection Security Alarms
In patient care areas equipped with an Infant Protection System, interface
with the Infant Protection System to receive and communicate infant
abduction alarm calls.
**************************************************************************
NOTE: If Patient Wandering Systems are NOT provided
SECTION 16731A