2.2.2
Emergency Push Button Stations
a.
Flush mount units.
b. A red color emergency push button call switch that is permanently
labeled as an Emergency call switch on or directly adjacent to the call
switch.
c. A call cancel push button switch that is clearly labeled "CANCEL".
Alternatively, the cancel function may be a toggle of the emergency call
switch.
d.
An LED call assurance indicator.
e. Stations installed in wet areas shall be water resistant and shall
comply with water spray exposure requirements of UL 1069.
f.
Waterproof gaskets for stations installed in wet areas.
2.2.3
Code Blue Stations
a.
Flush mount units.
b. A blue color code blue push button call switch with the term "CODE" or
"CODE BLUE" located on or directly adjacent to the push button.
c. A call cancel push button switch that is clearly labeled "CANCEL".
Alternatively, the cancel function may be a toggle of the code blue call
switch.
d.
An LED call assurance indicator.
2.2.4
Duty Stations
a.
Flush mount units.
b.
An electronic alert tone device.
2.2.5
Annunciator Stations
**************************************************************************
NOTE: Preferred configuration is flush wall mount.
Desk mount configuration should be specified only
when required by special circumstances.
**************************************************************************
a.
Configurations as shown:
[Type 1: Flush wall mount]
[Type 2: Desktop mount]
b.
Visual Indicator Display
(1) Electronic programmable visual indicator display. Acceptable
Incandescent lamp displays are not acceptable.
(2) The font size of the alphanumeric text call information displayed
shall be large enough to assure clear readability from the workstations in
the area where the annunciator is located.
SECTION 16730A