c. Submit a letter to the Contracting Officer from the Manufacturer
guaranteeing that the Manufacturer shall inform the Government of, and make
available to the Government, all commercially available enhancements to the
system hardware or software at the then current price. Include the letter
with the product data submittal.
d. Substitutions, modifications, or improvements to a system hardware and
software are permissible provided that such substitution, modifications, or
improvements shall not reduce or degrade the performance or product
requirements, nor violate regulatory requirements. No such substitutions,
modifications, or improvements shall be made without the written consent of
the Manufacturer and Contracting Officer. Such consent shall not be
unreasonably withheld or delayed.
2.1.8
Software and License
a. Provide all software required for the specified capability,
configuration, performance, and operation of the system.
b. The Government shall be granted a nonexclusive, fully paid perpetual
license to use software provided. The Government receives no title or
ownership rights to such Software.
c. Software maintenance that is provided to any or all other customers
without charge shall be provided to the Government at no additional cost to
the Government.
2.1.9
Equipment Design for Wet Areas
All equipment that will be installed in wet areas shall be designed and
constructed to withstand the UL 1069 Water Spray Test.
2.2
NC SUBSYSTEMS
2.2.1
Emergency Pull Cord Stations
a.
Flush mount units.
b. An emergency call switch that is activated by pulling a nylon cord
attached to the switch. The cord shall have a pendant attached to the end
of the cord, and length extended to within 50 mm 2 inches of the floor.
The term "PULL FOR HELP" shall be located directly adjacent to the call
switch.
c. A call cancel push button switch that is clearly labeled either
"CANCEL" or "RESET". Alternatively, the cancel function may be a toggle of
the emergency call switch. For stations installed in showers or baths that
are located in the same room as a toilet, it is acceptable to have the
cancel function for the shower/bath station operated from the adjacent
emergency pull cord toilet station.
d.
An LED call assurance indicator.
e. Stations installed in wet areas shall be water resistant and shall
comply with water spray exposure requirements of UL 1069.
f.
Waterproof gaskets for stations installed in wet areas.
SECTION 16730A