3.2.2
Annunciator Stations
**************************************************************************
NOTE: Include this paragraph if the NCTV System is
required to have annunciator stations.
**************************************************************************
The exact display panel configuration and details for all annunciator
stations shall be as coordinated with the Contracting Officer and the
medical facility user. Submit details as part of the shop drawings.
3.2.3
Interface with Other Products
**************************************************************************
NOTE: Include this paragraph if the NCTV System is
to be interfaced with a Radio Paging System and/or
the NCAV System.
**************************************************************************
with other products. This shall include a detailed definition of all
electronic and physical interface requirements, interface protocols, and
physical demarcation points. Provide details as part of shop drawings and
design data submittals.
3.3
INSTALLATION
3.3.1
General
a. Installation shall be accomplished as indicated and specified, and in
accordance with acknowledged industry and professional standards and
practices, and the Manufacturer's instructions.
b. Installation shall comply with the requirements of NFPA 70, NFPA 99,
and EIA ANSI/TIA/EIA-569-A.
c. The Installer as qualified in Paragraph QUALITY ASSURANCE, subparagrah
Installer Qualifications, shall install and connect all equipment and
system cabling.
d. During the entire installation the system Contractor shall maintain
onsite a supervisor as qualified in Paragraph QUALITY ASSURANCE,
subparagraph Installer Qualifications.
e.
Provide all tools and equipment needed to install the system.
f. All ac power plugs shall be tightly strapped to the ac power receptacle
to prevent accidental unplugging of the ac power.
3.3.2
Equipment Installation
a. Appropriate waterproof gaskets shall be used for station installations
in wet areas (toilet rooms, showers, etc.).
b. Main Terminal/Equipment Panels shall be surface mounted in the
telecommunications rooms indicated on the drawings. Mounting of these
panels in any other room, area or above finished ceilings shall not be
acceptable. Panels shall be marked by the NC Subsystem number and function
served.
SECTION 16730A