c. The system LAN, server, and UPS equipment housed in telecommunications
rooms shall be [rack] [cabinet] mounted. Under no circumstance shall any
of this equipment be mounted on the floor.
d.
Mount equipment firmly secured in place, plumb and square.
e. Provide adequate equipment ventilation and adequate equipment
accessibility for service and repair.
3.3.3
System Cabling Installation
**************************************************************************
NOTE: If the NCTV System is to be procured as part
of a facility construction project contract, include
item "c." below.
**************************************************************************
a.
Installation of system cabling shall be by the qualified Installer.
b. System cables shall be installed without kinks, sharp bends or
deformations, in a manner to prevent abrasion.
[c. System cabling shall be installed in cable trays, conduits and boxes
specified in Section 16402 INTERIOR DISTRIBUTION SYSTEM.]
3.3.4
Grounding
Equipment enclosures and all other non-current carrying metal parts of
electric equipment shall be grounded.
3.3.5
Related Trades
**************************************************************************
NOTE: If the NCTV System is to be procured as part
of a facility construction project contract, include
this paragraph.
**************************************************************************
a. Coordinate all efforts with those of related trades. In the event of
any conflicts, delayed or improper preparatory work by others, notify the
Contracting Officer for resolution; the Contracting Officers= decision
shall be binding.
b. The Electrical Contractor for the project shall furnish and install all
cable trays, conduits, boxes, grounding system and buss bars, and all
primary power wiring required to accommodate the installation of the system
specified in this Section.
c. Coordinate the system cable routing with the cable routing of other
systems to assure that there will not be any EMI problems that will
adversely affect the performance of this system or any other specified
project system.
3.3.6
Infrastructure and Rough-in - Facility Construction Project
**************************************************************************
NOTE: If the NCTV System is to be installed in a
facility construction project (new, addition or
SECTION 16730A
Page 38