transformers and switches shall be stored in accordance with the
manufacturer's requirements. Wood poles held in storage for more than 2
weeks shall be stored in accordance with ATIS O5.1. Handling of wood poles
shall be in accordance with ATIS O5.1, except that pointed tools capable of
producing indentations more than 25 mm 1 inch in depth shall not be used.
Metal poles shall be handled and stored in accordance with the
manufacturer's instructions.
1.5
EXTRA MATERIALS
One additional spare fuse or fuse element for each furnished fuse or fuse
element shall be delivered to the contracting officer when the electrical
system is accepted. Two complete sets of all special tools required for
maintenance shall be provided, complete with a suitable tool box. Special
tools are those that only the manufacturer provides, for special purposes
(to access compartments, or operate, adjust, or maintain special parts).
1.6
DRAWINGS
1.6.1
Detail Drawings
The Contractor shall submit detail drawings consisting of equipment
drawings, illustrations, schedules, instructions, diagrams manufacturers
standard installation drawings and other information necessary to define
the installation and enable the Government to check conformity with the
requirements of the contract drawings.
a. If departures from the contract drawings are deemed necessary by
the Contractor, complete details of such departures shall be included
with the detail drawings. Approved departures shall be made at no
additional cost to the Government.
together and how they will be installed on the project. Data and
drawings for component parts of an item or system shall be coordinated
and submitted as a unit. Data and drawings shall be coordinated and
included in a single submission. Multiple submissions for the same
equipment or system are not acceptable except where prior approval has
been obtained from the Contracting Officer. In such cases, a list of
data to be submitted later shall be included with the first submission.
Detail drawings shall consist of the following:
1). Detail drawings showing physical arrangement, construction
details, connections, finishes, materials used in fabrication,
provisions for conduit or busway entrance, access requirements for
installation and maintenance, physical size, electrical
characteristics, foundation and support details, and equipment
weight. Drawings shall be drawn to scale and/or dimensioned. All
optional items shall be clearly identified as included or excluded.
actually provided for this project. External wiring connections
shall be clearly identified.
the following items:
(a). Medium-voltage cables and accessories including cable
installation plan.
SECTION 16375A
Page 16