(b).
Transformers.
(c).
Substations.
(d).
Switchgear.
(e).
Pad-mounted loadbreak switches.
(f).
Busways.
(g).
Surge arresters.
1.6.2
As-Built Drawings
The as-built drawings shall be a record of the construction as installed.
The drawings shall include the information shown on the contract drawings
as well as deviations, modifications, and changes from the contract
drawings, however minor. The as-built drawings shall be a full sized set
of prints marked to reflect deviations, modifications, and changes. The
as-built drawings shall be complete and show the location, size,
dimensions, part identification, and other information. Additional sheets
may be added. The as-built drawings shall be jointly inspected for
accuracy and completeness by the Contractor's quality control
representative and by the Contracting Officer prior to the submission of
each monthly pay estimate. Upon completion of the work, the Contractor
shall provide three full sized sets of the marked prints to the Contracting
Officer for approval. If upon review, the as-built drawings are found to
contain errors and/or omissions, they will be returned to the Contractor
for correction. The Contractor shall correct and return the as-built
drawings to the Contracting Officer for approval within 10 calendar days
from the time the drawings are returned to the Contractor.
PART 2
PRODUCTS
2.1
STANDARD PRODUCT
Material and equipment shall be the standard product of a manufacturer
regularly engaged in the manufacture of the product and shall essentially
duplicate items that have been in satisfactory use for at least 2 years
prior to bid opening. Items of the same classification shall be identical
including equipment, assemblies, parts, and components.
2.2
NAMEPLATES
2.2.1
General
Each major component of this specification shall have the manufacturer's
name, address, type or style, model or serial number, and catalog number on
a nameplate securely attached to the equipment. Nameplates shall be made
of noncorrosive metal. Equipment containing liquid dielectrics shall have
the type of dielectric on the nameplate. Sectionalizer switch nameplates
shall have a schematic with all switch positions shown and labeled. As a
meters, switches, and switchgear.
2.2.2
**************************************************************************
SECTION 16375A
Page 17