2.1.3.1
600 Volt Wires and Cables
**************************************************************************
NOTE: Type THW insulation can only be obtained in
large quantity. Use of this type of insulation is
not recommended for smaller projects. Types USE and
THW are larger than THWN insulation. When they are
allowed ensure that the conduit has been properly
sized for the number of THW or USE wires indicated
in each conduit run.
**************************************************************************
Service entrance and direct buried conductors shall conform to UL 854, Type
USE. Conductors in conduit other than service entrance shall conform to UL
83, Type THWN [or THW]. Conductor size and number of conductors in each
cable shall be as indicated. Conductors shall be color coded. Conductor
identification shall be provided within each enclosure where a tap, splice,
or termination is made. Conductor identification shall be by color-coded
insulated conductors, plastic-coated self-sticking printed markers, colored
nylon cable ties and plates, or heat shrink type sleeves. Control circuit
terminations shall be properly identified. Conductors No. 10 AWG and
smaller shall be solid copper. Conductors No. 8 AWG and larger shall be
stranded copper. [All conductors shall be copper.] [Conductors No. 6 AWG
and smaller shall be copper. Conductors No. 4 AWG and larger shall be
either copper or aluminum, at the Contractor's option. Should the
Contractor opt to use aluminum, he shall be responsible for meeting the
requirements of the following paragraph, "Aluminum Conductors."] [As an
exception to the preceding statement, do not substitute aluminum for copper
if the equivalent aluminum size would exceed 500 KCMIL.]
a.
Colors for coding conductors shall be:
208-VOLT SYSTEM
480-VOLT SYSTEM
Neutral - White
Neutral - White
Phase A - Black
Phase A - Brown
Phase B - Red
Phase B - Orange
Phase C - Blue
Phase C - Yellow
Grounding conductor - Green
Grounding conductor - Green
[b.
Aluminum Conductors: Should the Contractor choose to use
aluminum for conductors No. 4 AWG and larger, the Contractor shall
be responsible for: Increasing the conductor size to have the
same ampacity as the copper size indicated; increasing the conduit
and pull box sizes to accommodate the larger size aluminum
conductors in accordance with NFPA 70; ensuring that the pulling
tension rating of the aluminum conductor is sufficient; relocating
equipment, modifying equipment terminations, resizing equipment,
and resolving to the satisfaction of the Contracting Officer
problems that are direct results of the use of aluminum conductors
in lieu of copper.]
(1) For 600-volt wiring, the aluminum conductors shall be of an
aluminum alloy listed or labeled by UL as "component aluminum-wire
stock (conductor material)." Type EC/1350 aluminum is not
acceptable.
(2) Equipment manufacturer requirements: Where Contractor
provides equipment whose manufacturer requires copper conductors
SECTION 16302N
Page 14