passed the following tests by the splice-termination manufacturer
or an independent testing laboratory.
_________________________________________________________________________
Minimum Value
TEST
5 kV
15 kV
35 kV
_________________________________________________________________________
Discharge Ext. Value with 3 pC or less
13 kV
20 kV
35 kV
AC withstand, 1 minute
35 kV
50 kV
75 kV
DC withstand, 15 minutes
65 kV
70 kV
100 kV
_________________________________________________________________________
These results shall be attached for review
(3) A statement of the number of years in which the individual
has been splicing/terminating medium voltage cable.
b.
Criteria for waiver: Items a.1 and a.2 above may be waived on
subsequent jobs provided the following criteria is satisfied:
(1) Documentation of prior completion of items a.1 and a.2 be
submitted.
(2) A list of the last three jobs where the specific
splices/terminations were installed within the past 12 consecutive
months. The tabulation shall include splice/termination
manufacturer, catalog number, and the number of
splice/terminations installed.
c.
Requalifications: Requalification to items a.1 and a.2 in above
paragraph may be required if the splice installer can not
demonstrate a prior history of splice/termination installation
during the previous 12 consecutive months. The contractor shall
furnish the material for splices and terminations.
1.5.2
Test Instrument and Procedure
**************************************************************************
NOTE: Delete this paragraph for LANTNAVFACENGCOM
projects.
**************************************************************************
Submit for use of ground megger with proposed method indicated.
1.5.3
Manufacturer's Test
**************************************************************************
NOTE: Delete this paragraph for LANTNAVFACENGCOM
projects.
**************************************************************************
Submit the manufacturer's test report indicating that performance of the
heat shrinkable joint kit is equivalent to the cable rating, in accordance
with the applicable sections of IEEE Std 48, IEEE Std 404, and AEIC CS1.