a.
Cold-Shrink Type:
**************************************************************************
NOTE: For Public Works Center, Pearl Harbor areas
and systems, this type shall not be specified/
included in contract specifications.
**************************************************************************
Terminator shall be a one-piece design, where high-dielectric constant
(capacitive) stress control is integrated within a skirted insulator made
of silicone rubber, munsel gray in color. Termination shall not require
heat or flame for installation. Termination kit shall contain all
necessary materials (except for the lugs). Termination shall be designed
for installation in low or highly contaminated indoor and outdoor locations
and shall be rated for continuous operation at 90 degree C, with an
emergency overload temperature rating of 130 degree C.
b.
Porcelain Insulator Type
Terminator shall comply with requirements of IEEE Std 48 Class 1, except
that the requirements of design tightness test need not be met. However,
the terminator shall not exude any insulating filler compound under either
test or service. Terminator shall consist of a porcelain insulator, copper
cable connector-hoodnut assembly and copper aerial lug as required, metal
body and supporting bracket, sealed cable entrance, internal stress relief
device for shielded cable, and insulating filler compound or material.
][2.1.7.3
Termination; Separable Insulated Connector Type
Provide as specified in Section [16272 PAD-MOUNTED TRANSFORMERS] [_____].
]2.1.7.4
Cast Epoxy Resin Type Termination
**************************************************************************
NOTE: Delete this paragragh for LANTNAVFACENGCOM
projects.
**************************************************************************
IEEE Std 48, Class 1. Provide termination as specified herein for
terminating single conductor, or the single conductors of multiconductor,
solid insulated, nonmetallic jacketed type cables for service voltage up to
15 KV outdoor and 15 KV indoor. Terminations for shielded conductors shall
include stress control, with a shield ground connection brought out through
the insulation and covering, and grounded at installation. Terminations
exposed to the weather shall include porcelain insulator and weather shield.
2.1.7.5
Terminator, Modular, Molded Rubber Type
**************************************************************************
NOTE: Delete this paragraph for LANTNAVFACENGCOM
projects.
**************************************************************************
IEEE Std 48 Class 1. Provide terminator as specified herein for
terminating single conductor, or the single conductor of multiconductor,
solid insulated, nonmetallic jacketed type cables for service voltage up to
35 KV outdoor. Terminator shall consist of a stress control, ground clamp,
nontracking rubber skirts, crimp-on connector, rubber cap, and aerial lug.
Do not use separate parts of copper or copper alloy in contact with
SECTION 16302N
Page 18