instructions.
Cold-shrink rubber-type joints are limited to 8.7
kV systems.]
[2.1.9
Live End Caps
Provide live end caps using a "kit" including a heat-shrinkable tube and a
cap shall conform to applicable portions of IEEE Std 48.
]2.1.10
Tape
2.1.10.1
Insulating Tape
UL 510, plastic insulating tape, capable of performing in a continuous
temperature environment of 80 degrees C.
2.1.10.2
Buried Warning and Identification Tape
Provide detectable aluminum foil plastic-backed tape or detectable magnetic
plastic tape manufactured specifically for warning and identification of
buried cable and conduit. Tape shall be detectable by an electronic
detection instrument. Provide tape in rolls, 50 mm 2 inchesminimum width,
color coded for the utility involved with warning and identification
imprinted in bold black letters continuously and repeatedly over entire
tape length. Warning and identification shall be CAUTION BURIED [ELECTRIC]
[,] [TELEPHONE] CABLE BELOW or similar. Use permanent code and letter
coloring unaffected by moisture and other substances contained in trench
2.1.10.3
Fireproofing Tape
**************************************************************************
NOTE: For LANTNAVFACENGCOM, use the second
bracketed paragraph.
**************************************************************************
[Fireproofing tape shall be approximately 0.762 mm thick by 75 mm 30 mils
thick by 3 inches wide and shall consist of a flexible, unsupported
elastomer that expands in fire to provide a thick char buildup between the
flame and the cable. Tape shall be noncorrosive to cable sheath. Tape
shall not give off a smoke when subjected to flame or support combustion.
Tape shall not deteriorate when subjected to oil, water, gases, salt water,
sewage, and fungus.]
[Furnish tape composed of a flexible conformable unsupported intumescent
elastomer. Tape shall be not less than 0.762 mm .030 inch thick,
noncorrosive to cable sheath, self-extinguishing, noncombustible, and shall
not deteriorate when subjected to oil, water, gases, salt water, sewage,
and fungus.]
2.1.11
Pull Rope
Shall be plastic having a minimum tensile strength of 890 N 200 pounds.
[Leave a minimum of 610 mm 24 inches of slack at each end of the pull
wires.]
2.1.12
UL 467.
Ground rods shall be copper clad steel with diameter adequate to
SECTION 16302N