1.4.9
Experience
Each component manufacturer shall have a minimum of 3 years experience in
the manufacture, assembly and sale of components used with stationary
diesel engine-generator sets for commercial and industrial use. The
engine-generator set manufacture/assembler shall have a minimum of 3 years
experience in the manufacture, assembly and sale of stationary diesel
engine-generator sets for commercial and industrial use.
1.4.10
Field Engineer
The engine-generator set manufacturer or assembler shall furnish a
qualified field engineer to supervise the complete installation of the
engine-generator set, assist in the performance of the onsite tests, and
instruct personnel as to the operational and maintenance features of the
equipment. The field engineer shall have attended the engine-generator
manufacturer's training courses on installation and operation and
maintenance for engine generator sets.
1.4.11
Seismic Requirements
**************************************************************************
NOTE: Provide seismic requirements, if a Government
designer (either Corps office or A/E) is the
Engineer of Record, and show on the drawings.
Delete the bracketed phrase if no seismic details
are provided. Sections 13080, 15070A, and 16070A,
properly edited, must be included in the contract
documents.
**************************************************************************
Seismic requirements shall be in accordance with Sections 13080 SEISMIC
PROTECTION FOR MISCELLANEOUS EQUIPMENT, 15070A SEISMIC PROTECTION FOR
MECHANICAL EQUIPMENT and 16070A SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
[as shown on the drawings].
1.4.12
Detailed Drawings
The Contractor shall submit detailed drawings showing the following:
a. Base-mounted equipment, complete with base and attachments
including anchor bolt template and recommended clearances for
maintenance and operation.
b.
Starting system.
c.
d.
e.
f. Electric wiring of relays, breakers, programmable
controllers, and switches including single line and wiring
diagrams.
g. Lubrication system, including piping, pumps, strainers,
SECTION 16264A
Page 26