Max Summer Outdoor Temp
[_____] degrees
(Ambient)
Min Winter Outdoor Temp
[_____] degrees
(Ambient)
Installation Elevation
[_____] above sea level
1.3.2
Output Capacity
**************************************************************************
NOTE: The service load for each genset should be
shown on the Engine-Generator Parameter Schedule.
The designer has control over the service load. The
Contractor through the supplier's
manufacturer/assembler has control of the efficiency
and associated ancillary equipment loads.
**************************************************************************
Each generator set shall provide power equal to the sum of service load
plus the machine's efficiency loss and associated ancillary equipment
loads. Rated output capacity shall also consider engine and/or generator
oversizing required to meet requirements in paragraph Engine-Generator
Parameter Schedule.
1.3.3
Power Rating
Standby ratings shall be in accordance with EGSA 101P.
1.4
GENERAL REQUIREMENTS
1.4.1
Engine-Generator Set
Each set shall consist of one engine, one generator, and one exciter,
mounted, assembled, and aligned on one base; and all other necessary
ancillary equipment which may be mounted separately. Sets shall be
assembled and attached to the base prior to shipping. Set components shall
be environmentally suitable for the locations shown and shall be the
manufacturer's standard product offered in catalogs for commercial or
industrial use. A generator strip heater shall be provided for moisture
control when the generator is not operating.
1.4.2
Nameplates
**************************************************************************
NOTE: Delete any equipment not applicable to the
project.
**************************************************************************
Each major component of this specification shall have the manufacturer's
name, type or style, model or serial number, and rating number on a plate
secured to the equipment. As a minimum, nameplates shall be provided for:
Pumps and pump motors; Governors; Generator Breaker; Economizers; Heat
exchangers (other than base-mounted).
Engines
SECTION 16264A
Page 23