Motor Starting kVA (maximum)
[_____] kVA
Maximum Speed
1800 rpm
Engine-Generator Application
stand-alone
Engine Cooling Type
water/ethylene glycol
[fin-tube] [shell-tube]
[Governor Type
Isochronous
+ [_____] [0.4] [0.25]%
steady state]
[Governor Type
Droop
[[3] [_____]% (max.)]
(No load to full load)
+ [_____] [0.4] [0.25]%
(steady state)]
+ 2% (max.)
(No load to full load)
+ [0.5] [1] [2]%
(steady state)
Frequency
[50] [60] Hz
Voltage
[_____] volts
Phases
[3 Phase, Wye] [3 Phase,
Delta] [1 Phase]
[_____] percent
Subtransient Reactance
Nonlinear Loads
[_____] kVA
Max Step Load Increase
[_____] [100]% of Service
Load at [_____] PF
Max Step Load Decrease
100 % of Service Load at
(without shutdown)
[_____] PF
Max Time to Start and be Ready to
[10] [_____] seconds
Assume Load
Max Summer Indoor Temp
[_____] degrees
(Prior to Genset Operation)
Min Winter Indoor Temp
[_____] degrees
(Prior to Genset Operation)
Max Allowable Heat Transferred
[_____] MBTUH/hr.
Rated Output Capacity
SECTION 16264A