Acceptance[; G][; G, [_____]]
Drawings which accurately depict the as-built configuration of
the installation, upon acceptance of the diesel-generator set
installation. Layout drawings shall be revised to reflect the
as-built conditions and submitted with the as-built drawings.
SD-03 Product Data
Performance Tests
Calculations of the engine and generator output power
capability, including efficiency and parasitic load data.
Sound Limitations[; G][; G, [_____]]
Sound power level data for the packaged unit operating at 100%
load in a free field environment. The data should demonstrate
compliance with the sound limitation requirements of this
specification.
Generator
Each generator KW rating and short circuit capacity (both
symmetric and asymmetric).
Integral Main Fuel Storage Tank
Day Tank
Calculations for the capacity of each day tank, including
allowances for recirculated fuel, usable tank capacity, and
Power Factor
Generator capability curve showing generator kVA output (kW vs.
kvar) for both leading and lagging power factors ranging from 0 to
1.0.
Manufacturers data to quantify heat rejected to the space with
the engine generator set at rated capacity.
Time-Delay on Alarms
The magnitude of monitored values which define alarm or action
setpoints, and the tolerance (plus and/or minus) at which the
device activates the alarm or action.
Cooling System
a. The maximum and minimum allowable inlet temperatures of the
[coolant fluid][cooling air].
b. The maximum allowable temperature rise in the [coolant fluid
through the engine][cooling air across the engine].
SECTION 16264A