SECTION 16264A
DIESEL-GENERATOR SET, STATIONARY 15-300 KW, STANDBY APPLICATIONS
12/04
**************************************************************************
NOTE: This guide specification covers the
requirements for stationary diesel driven generator
sets in the 15 to 300 kilowatt capacity for standby
applications.
Comments and suggestions on this guide specification
are welcome and should be directed to the technical
proponent of the specification. A listing of
technical proponents, including their organization
designation and telephone number, is on the Internet.
Recommended changes to a UFGS should be submitted as
a Criteria Change Request (CCR).
Use of electronic communication is encouraged.
Brackets are used in the text to indicate designer
choices or locations where text must be supplied by
the designer.
**************************************************************************
PART 1
GENERAL
**************************************************************************
NOTE: This specification is for procurement of
engine-generator sets which are suitable for serving
general purpose and commercial-grade loads (loads
which may be served by an electric utility). These
are loads which can endure or recover quickly from
transient voltage and frequency changes (as much as
30 percent transient voltage drop, and plus or minus
5 percent frequency deviation, with recovery time of
2 seconds). For applications where strict control
of voltage, frequency, and transient response is
required, provide uninterruptible power supplies or
utilize UFGS-16263A. This specification is for
procurement of engine-generator sets for standby,
stand-alone applications. For prime or parallel
SECTION 16264A